Evaluation of Corrosion and Scaling Potential of a Water Treatment Plant
Edris Hoseinzadeh , Abdolrahim Yusefzadeh , Naser Rahimi *, Hassan Khorsandi
Takab Health Center, Urmia University of Medical Sciences, Urmia, Iran.
Abstract:   (956 Views)

 Background & Aims of the Study: We evaluated corrosion and scaling potential of water treated by “Takab city (Western Iran) water treatment plant (called Chahar Tagh facilities)” using field observation of water treatment plant, and study of physical and chemical parameter values of water.

Materials & Methods: In this cross-sectional study, during a 10-month period (from January to October 2012) in each month, 15 grab samples with 2 to 3 L of water were collected for analysis. Some physical and chemical parameters such as temperature, pH, total dissolved solids, calcium and magnesium hardness, calcium and magnesium ions concentration, total alkalinity, bicarbonate concentration and electrical conductivity were measured. The corrosion and scaling potential of water were calculated by Langelier saturation index (LSI), Risnar index (RI), aggressive index (AI) and Puckorius scaling index (PSI).

Results: Values recorded for all physicochemical parameters were in acceptable standard levels. The calculated values of LSI index indicated slightly scale forming and corrosive, RI index showed heavy corrosion, AI index showed water is non-aggressive and based on PSI index results water is likely to dissolve scale. Based on LSI, RI, AI and PSI monthly indices results the water of water treatment plant showed a uniform quality of corrosion and precipitation potential.

Conclusions: The results showed that values of all measured physical and chemical parameters were in the range of national and international standards. Based on LSI and AI indices results, water tends to scale forming while based on RI and PSI indices results water tend to be corrosive.

Keywords: Aggressive Index, Langelier Saturation Index, Puckorius Scaling Index, Ryznar Stability Index, Takab, Iran, Water Corrosion Index, Water Scaling Index, Water Treatment Plant
Full-Text [PDF 282 kb]   (989 Downloads)    
Type of Study: Research | Subject: General
Received: 2016/02/13 | Accepted: 2016/02/23 | Published: 2016/02/23
Send email to the article author

Add your comments about this article
Your username or Email:

Write the security code in the box >



XML     Print


Download citation:
BibTeX | RIS | EndNote | Medlars | ProCite | Reference Manager | RefWorks
Send citation to:

Hoseinzadeh E, Yusefzadeh A, Rahimi N, Khorsandi H. Evaluation of Corrosion and Scaling Potential of a Water Treatment Plant. Arch Hyg Sci. 2013; 2 (2) :41-47
URL: http://jhygiene.muq.ac.ir/article-1-11-en.html
Volume 2, Issue 2 (Spring 2013 2013) Back to browse issues page
Archives of Hygiene Sciences Archives of Hygiene Sciences
Persian site map - English site map - Created in 0.152 seconds with 804 queries by yektaweb 3510